Braided shunts sect.85 mm²

Braided shunts for 320 A switch.

Braided shunts sect.85 mm²

J-LINK

CodeReferenceDimensions (mm)Rated Intensity In (A) Temperature Rise in T
  LBHL1L2d1d2s45°C35°C25°C
JLK1140JLK 85-23023025249,5118,510,56,5350320270
JLK1145JLK 85-33033025249,5118,510,56,5
JLK1150JLK 85-43043025249,5118,510,56,5
JLK1155JLK 85-53053025249,5118,510,56,5
JLK1160JLK 85-63063025249,5118,510,56,5
JLK1165JLK 85-73073025249,5118,510,56,5
JLK1170JLK 85-83083025249,5118,510,56,5
JLK1175JLK 85-93093025249,5118,510,56,5
JLK1180JLK 85-1030103025249,5118,510,56,5

J-LINK PLUS

CodeReferenceDimensions (mm)Rated Intensity In (A) Temperature Rise in T
  LBHL1L2d1d2s45°C35°C25°C
JLK5140JLP 85-23023025249,5118,510,56,5350320270
JLK5145JLP 85-33033025249,5118,510,56,5
JLK5150JLP 85-43043025249,5118,510,56,5
JLK5155JLP 85-53053025249,5118,510,56,5
JLK5160JLP 85-63063025249,5118,510,56,5
JLK5165JLP 85-73073025249,5118,510,56,5
JLK5170JLP 85-83083025249,5118,510,56,5
JLK5175JLP 85-93093025249,5118,510,56,5
JLK5180JLP 85-1030103025249,5118,510,56,5

Packaging: 2

Table of ampacities (A) based on the switch ampacity or on the T temperature rise as per standard IEC 61439-1
Reference room temperature 40°C

Derating coefficient for use of J-LINK in parallel

Cross-section  (mm²)IIIII
251,702,00
351,702,00
501,701,95
1201,651,85
2401,551,75